Product Details:
Payment & Shipping Terms:
|
Voltage Range: | 0-576V | Current Range: | 5....3000A (clamp) |
---|---|---|---|
HV Current Clamp: | 35KV & 360A | Test Function: | Meter Error, Power, Energy...etc |
Application: | Worksite | User Type: | Utilities. Service Company |
Accuracy Class: | 0.2 | HV Current Clamp Class: | 2 |
High Light: | 360A Energy Meter Calibration Equipment,360A utilities Energy Meter Calibration Equipment,anti theft 360A multifunction test meter |
Portable Multifuction Meter Test & Monitor System MC300
1) High Stability and suitable for field complicate working conditions
2) Accurate test and transmission
3) Suitable for meter test, electrical parameter test, anti-theft and etc.
4) Comprising of iPad, main unit, wireless receiver, current clamp, HV Current clamp and etc.
Technical Index
Voltage Measurement | |
Inner range | 480V,120V,30V |
Extension range of A phase | 7.5V,1.88V,0.47V;(for CT secondary burden test) |
Test Range | (0V~576V, A phase) 6V~576V |
Accuracy | <0.3% |
Current measurement | |
Range (clamp mode) | 5A…500A…1000A, accuracy 0.2% |
HV Current clamp | Max 35KV & 360A, Accuracy 2% |
Phase Measurement | |
Range | 0.00°~359.99° |
Resolution | 0.01° |
Accuracy | 0.2° |
Power & Energy Measurement | |
Accuracy (P, S) | 0.2% |
Accuracy (Q) | 0.5% |
Frequency Measurement | |
Range | 45-65HZ |
Resolution | 0.01 HZ |
Accuracy | 0.1HZ |
Other Parameters | |
Auxiliary Supply | AC 100-240V, 50/60HZ |
Whole power consumption when charging battery |
7 VA(max)
|
Working power consumption | 2.5VA(max) |
Battery continuously working time after charging |
more than 7 hours
|
Charging time(main unit and wireless receiver) | around 6 hours |
Charging time(HV current clamp) | around 6 hours |
Size & Weight | |
Main unit | 170mm×125mm×64mm & 0.72KG |
Wireless receiver | 170mm×125mm×64mm & 0.62KG |
HV current clamp | 250mm×77mm×31mm & 0.32KG |
Features
1) Active & Reactive Pulse Error test & Dial Test of Energy Meter
2) Comprehensive Error Test of Metering unit of LV panel with CT
3) Reading parameter of Energy Meter by RS485 or infrared sensor
4) Query function of energy meter event records
5) Real-time check of voltage, current and time section of energy meter
6) Wiring check & analysis function for 3P3W, 3P4W
7) Wiring check for meter facility with phase check function
8) Real-time display of electrical parameters, vector diagram, six phases waveform and 64 times harmonics.
9) Ratio test of high & low voltage, CT/PT burden test
10) On-spot photograph, recording sound, videotape, meter bar code scanning
Contact Person: Mr. Tony Han
Tel: 86-15237157117
Fax: 86-371-55692730