Induction Voltage Divider HJF3
1. Usage
HJF3 type induction voltage divider is used for testing and calibration of voltage transformer
whose ratio is different from standard voltage transformer.
In general, the secondary load of standard VT is 0.2VA(100V) or 0.07VA(100/√3V); total exciting
power of primary and secondary is only 0.05VA (100V), so it will not give influence on accuracy when
connecting secondary of standard VT.
2. Technical Parameters
Accuracy class |
0.001 |
Input voltage | 100V, 200V |
Output voltage |
2х10-4V~222.222V |
Rated Frequency | 50HZ or 60HZ |
Working temperature |
5~55℃ |
Customization is available.
Notice Points
1. Waveform of power source should be sine wave, and distortion should be less than 5%, and
frequency variation should be ±0.5HZ
2. Don’t have noxious gas or other dielectric in the worksite which will give influence on insulation
of voltage transformer
3. Don’t have heavy shaking at site
4. Should not have external strong magnetic field in the test site.